Electrical Tools · NEC 2023 · Free

Breaker Size Calculator — The 125% Rule

Sizing an overcurrent device is three steps: take non-continuous load at 100% and continuous load at 125%, round up to the next standard rating in NEC 240.6(A), then make sure the conductor is large enough to be protected by that device. This calculator does all three and shows you the 240.4(D) small-conductor cap when it applies.

Size the overcurrent device

amps
0400 A

Runs three hours or more at maximum current — counted at 125%.

amps

Cycling or intermittent load — counted at 100%.

Used only to show the load in VA — it does not affect the breaker size.

Required breaker

50 A

50 A is already a standard 240.6(A) rating — no rounding needed.

Required amps

50.0 A

Minimum conductor

8 AWG copper

See the breakdown
Non-continuous at 100%
Continuous at 125%
Total required
Next standard rating
Conductor to match
Its ampacity
Connected load

Conductor shown is the general-purpose minimum before derating. Motor and air-conditioning circuits follow Articles 430 and 440, where the device may exceed conductor ampacity.

The formula, explained in plain English

Three steps, in a fixed order. Skipping the third is how undersized conductors end up behind correctly sized breakers.

# Step 1 — Weight the loads (NEC 210.20(A))
required = non-continuous × 1.00 + continuous × 1.25
# Step 2 — Round up to a real device (NEC 240.6(A))
OCPD = smallest of 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200… ≥ required
# Step 3 — The conductor must survive that device (NEC 240.4)
conductor = smallest AWG whose ampacity ≥ OCPD, subject to 240.4(D)
# The 80% rule, restated
1 ÷ 1.25 = 0.80  →  a continuous load may not exceed 80% of the breaker rating

125% and 80% are the same rule

Sizing the breaker at 125% of a continuous load is arithmetically identical to loading a breaker to no more than 80% of its rating. The Code writes it the first way; the trade says it the second way.

Round up, never down

51 A of required capacity means a 60 A device, because a 50 A breaker would nuisance-trip. That jump can also push the conductor from 6 AWG to 4 AWG.

The breaker guards the wire

NEC 240.4 exists to keep conductors from carrying more than their ampacity. Equipment looks after itself through internal protection or a nameplate MOCP value.

Motors break the pattern

Article 430 splits the job: the breaker handles short circuits and ground faults, a separate overload device handles sustained overcurrent. That is why motor breakers legitimately exceed conductor ampacity.

Worked examples

A clean landing, the rounding surprise, and the case that explains why a 16 A continuous load cannot sit on a 15 A circuit.

1

40 A continuous — EV charger or commercial lighting

40 A continuous · 0 A non-continuous · copper · 75 °C terminations. The defaults above.

required = 0 × 1.00 + 40 × 1.25 = 50.0 A
50 A is already a standard 240.6(A) rating
conductor: 8 AWG Cu = 50 A at 75 °C ✓
50 A breaker · 8 AWG copper

Result: the arithmetic lands exactly on a standard rating, and the conductor's ampacity matches the device exactly. This is as tidy as circuit sizing gets.

2

Mixed load — 36 A non-continuous + 12 A continuous

Copper · 75 °C terminations.

required = 36 × 1.00 + 12 × 1.25 = 36 + 15 = 51.0 A
51 A is not standard → round up to 60 A
conductor: 8 AWG (50 A) is too small → 6 AWG Cu = 65 A ✓
60 A breaker · 6 AWG copper

Result: one amp over 50 costs a whole conductor size. A 48 A total load would have stayed on a 50 A breaker with 8 AWG — worth knowing before adding that last fixture to a circuit.

3

16 A continuous — the 15 amp circuit that can't

Copper · 75 °C terminations.

required = 16 × 1.25 = 20.0 A
→ 20 A breaker · 12 AWG Cu (capped at 20 A by 240.4(D))
on a 15 A circuit: 15 × 0.80 = 12 A maximum continuous

Result: a 15 A circuit can only carry 12 A continuously, so a 16 A continuous load needs a 20 A circuit on 12 AWG. This is the calculation behind most commercial lighting-circuit layouts.

Standard breaker sizes and matching conductors

Every standard rating from NEC 240.6(A) up to 200 A, with the smallest general-purpose conductor at the 75 °C column that the device may protect. Rows marked with a cap are limited by the 240.4(D) small-conductor rule. Dwelling services and main feeders are smaller — those use Table 310.12 and the 83% allowance instead.

Breaker Max continuous load (80%) Copper (75 °C) Aluminum (75 °C)
15 A 12 A 14 AWG 240.4(D) 12 AWG
20 A 16 A 12 AWG 240.4(D) 10 AWG
25 A 20 A 10 AWG 240.4(D) 10 AWG
30 A 24 A 10 AWG 240.4(D) 8 AWG
35 A 28 A 8 AWG 8 AWG
40 A 32 A 8 AWG 8 AWG
45 A 36 A 8 AWG 6 AWG
50 A 40 A 8 AWG 6 AWG
60 A 48 A 6 AWG 4 AWG
70 A 56 A 4 AWG 3 AWG
80 A 64 A 4 AWG 2 AWG
90 A 72 A 3 AWG 2 AWG
100 A 80 A 3 AWG 1 AWG
110 A 88 A 2 AWG 1/0 AWG
125 A 100 A 1 AWG 2/0 AWG
150 A 120 A 1/0 AWG 3/0 AWG
175 A 140 A 2/0 AWG 4/0 AWG
200 A 160 A 3/0 AWG 250 kcmil

Sources & standards: NEC (NFPA 70) 2023 — 210.20(A) overcurrent device rating, Article 100 definition of continuous load, 240.6(A) standard ampere ratings, 240.4 conductor protection, 240.4(B) next-higher-rating allowance, 240.4(D) small-conductor limits, 240.4(G) and Articles 430 and 440 for motor and air-conditioning circuits, Table 310.16 ampacities. Local amendments override the model code.

Frequently asked questions

Common questions about breaker sizing, continuous loads, and the 80% rule.

What is a continuous load?

NEC Article 100 defines it as a load where the maximum current is expected to continue for three hours or more. Commercial lighting, EV charging, electric water heating on a long recovery, and most commercial refrigeration qualify. Household receptacle circuits, ranges, and dryers generally do not — they cycle. When in doubt, treating a load as continuous is the conservative choice.

Why 125% for continuous loads?

Because a breaker carrying its full rating continuously runs hot, and heat is cumulative. NEC 210.20(A) requires the overcurrent device to be rated at not less than 100% of the non-continuous load plus 125% of the continuous load. The inverse of 1.25 is 0.80 — which is where the informal "80% rule" comes from. They are the same requirement stated from opposite ends.

Can I use a 40 amp breaker on 10 AWG wire?

No. NEC 240.4(D) caps 10 AWG copper at a 30 A overcurrent device regardless of what Table 310.16 says its ampacity is, and caps 12 AWG copper at 20 A and 14 AWG copper at 15 A. For aluminum the caps are 25 A on 10 AWG and 15 A on 12 AWG. The narrow exceptions are motor and air-conditioning circuits, where Articles 430 and 440 permit the device to exceed conductor ampacity because it is protecting against short circuits rather than overload.

What are the standard breaker sizes?

NEC 240.6(A) lists them: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, and 600 amps, continuing upward from there. Anything not on that list is a non-standard rating — available as a special order but not something to design around.

What if my calculated amps fall between two standard sizes?

You round up to the next standard rating. A 51 A calculated requirement goes to a 60 A device, not 50 A. This surprises people because it feels like over-protection, but the breaker is sized to carry the load without nuisance tripping — the conductor then has to be large enough for that breaker, which is why rounding up can push the wire up a size too.

Does the breaker protect the wire or the equipment?

Primarily the wire. That is the core logic of NEC 240.4: overcurrent devices protect conductors from carrying more current than their ampacity allows. Equipment protection is a separate matter handled by the appliance's own internal protection, or by the nameplate's maximum overcurrent protection rating for HVAC equipment. This is why the breaker can never simply be sized to "whatever the appliance wants."

When is a breaker allowed to be larger than the conductor ampacity?

Several specific cases. 240.4(G) lists them, and motor circuits (Article 430) are the big one — the branch-circuit device there provides short-circuit and ground-fault protection while a separate overload relay handles sustained overcurrent, so a 60 A breaker on conductors rated 40 A is normal. Air-conditioning equipment (Article 440) works the same way, which is why nameplates give a minimum circuit ampacity and a separate maximum overcurrent protection value. For HVAC, the HVAC Amp Draw Calculator works out MCA and MOCP from BTU capacity.

Breaker sized? Quote the circuit in seconds.

The device is one line; the circuit is a dozen. Describe the job or upload photos and TradesQuote's AI builds a detailed line-item estimate — breaker, conductor, raceway, devices, and labor — with quantities and totals, validated by a built-in quality control agent.

AI line-item estimates

Quantities, unit prices, and totals generated instantly.

Knowledge base

Upload past jobs so estimates reflect your real pricing.

Shareable & signable

Clients review, accept, and sign from a public link.

No credit card required · 14-day free trial · Cancel anytime

More electrical calculators