Service Wire Size Calculator — The 83% Rule
Dwelling services get their own conductor table. NEC Table 310.12 permits a house's service — or the single feeder carrying its entire load — to use conductors rated at 83% of the service rating, which is why 4/0 aluminum legitimately serves a 200 A house. Get the type selector wrong and you get the wrong answer, so this calculator makes the distinction explicit and falls back to Table 310.16 when the 83% allowance doesn't apply.
Size the service conductors
This single choice decides whether the 83% allowance applies. It is the most common source of error on this calculation.
Ungrounded conductors
Table 310.12 allows 4/0 AWG aluminum for a 200 A dwelling service — the 83% allowance.
Neutral
—
Grounding electrode conductor
—
See the breakdown
GEC shown assumes a concrete-encased electrode. A rod-only electrode caps it at 6 AWG copper (250.66(A)). Terminations must be listed for the conductor material, and aluminum needs the correct compound and torque.
The formula, explained in plain English
One decision, then one lookup. The decision matters more than the lookup.
Why dwellings get a break
A house's calculated load already has demand factors baked in, and real peaks are short. The 83% allowance recognises that a 200 A residential service almost never sees 200 A long enough to heat a conductor to its limit.
"Entire load" is the test
The allowance covers the service and the one feeder that carries everything. Split the load across two feeders and neither qualifies — both go back to Table 310.16.
The reduced neutral
240 V loads like ranges, dryers, and AC put nothing on the neutral, so 220.61 lets it shrink. That's why 4/0-4/0-2/0 aluminum SER exists as a stock item.
Long runs still bite
A 200 A service 250 feet from the transformer needs more copper than the table says. Rural and long-driveway services are where the voltage-drop check earns its keep.
Worked examples
The standard 200 A service, the garage subpanel that catches everyone, and a long run that beats the table.
200 A house service — 100 ft, aluminum
Dwelling service · aluminum · 100 ft · 240 V. The defaults above.
Table 310.12, 200 A aluminum → 4/0 AWG
drop = 2 × 21.2 × 200 × 100 ÷ 211,600 = 4.01 V = 1.67% ✓
GEC (Table 250.66, 4/0 Al service) = 4 AWG copper
→ 4/0 aluminum · 4 AWG copper GEC
Result: the most common residential service in the United States. Note that Table 310.16 rates 4/0 aluminum at only 180 A — the 83% allowance is what makes this legal.
200 A detached garage subpanel — the trap
Not a dwelling service and not carrying the whole load · aluminum · 240 V.
Table 310.16, 75 °C aluminum: 4/0 = 180 A < 200 A ✗
next size: 250 kcmil aluminum = 205 A ✓
→ 250 kcmil aluminum, or 2/0 copper
Result: the same 4/0 aluminum that serves a 200 A house is undersized for a 200 A garage feeder. This is the single most common error in online electrical advice, and it fails inspection.
100 A service, 150 ft, copper — drop governs
Dwelling service · copper · 150 ft · 240 V.
4 AWG drop = 2 × 12.9 × 100 × 150 ÷ 41,740 = 9.27 V = 3.86% ✗
3 AWG = 7.36 V = 3.06% ✗ · 2 AWG = 5.83 V = 2.43% ✓
→ 2 AWG copper — two sizes up from the table
Result: the table gets you 4 AWG; 150 feet of run costs two more sizes. Long services from a pole or a distant transformer routinely land here.
Table 310.12 vs Table 310.16 — what the 83% allowance buys
The left pair is what a dwelling service may use. The right pair is what the same rating needs as any other feeder. The gap is usually one conductor size, and occasionally two.
| Rating | Cu — dwelling | Al — dwelling | Cu — other feeder | Al — other feeder |
|---|---|---|---|---|
| 100 A | 4 AWG | 2 AWG | 3 AWG | 1 AWG |
| 110 A | 3 AWG | 1 AWG | 2 AWG | 1/0 AWG |
| 125 A | 2 AWG | 1/0 AWG | 1 AWG | 2/0 AWG |
| 150 A | 1 AWG | 2/0 AWG | 1/0 AWG | 3/0 AWG |
| 175 A | 1/0 AWG | 3/0 AWG | 2/0 AWG | 4/0 AWG |
| 200 A | 2/0 AWG | 4/0 AWG | 3/0 AWG | 250 kcmil |
| 225 A | 3/0 AWG | 250 kcmil | 4/0 AWG | 300 kcmil |
| 250 A | 4/0 AWG | 300 kcmil | 250 kcmil | 350 kcmil |
| 300 A | 250 kcmil | 350 kcmil | 350 kcmil | 500 kcmil |
| 350 A | 350 kcmil | 500 kcmil | 500 kcmil | parallel sets |
| 400 A | 400 kcmil | 600 kcmil | 600 kcmil | parallel sets |
Sources & standards: NEC (NFPA 70) 2023 — Table 310.12 dwelling services and feeders, Table 310.16 conductor ampacities, 220.61 neutral load, 250.24(C) minimum service neutral, Table 250.66 grounding electrode conductor, 110.14(C) termination temperature, 230.42 service conductor sizing, 210.19(A) Informational Note on voltage drop. Local amendments and utility requirements override the model code.
Frequently asked questions
Common questions about service conductors, the 83% rule, and subpanel feeders.
What size wire for a 200 amp service?
For a dwelling service or the main feeder carrying the whole load, NEC Table 310.12 allows 2/0 copper or 4/0 aluminum. Both are one size smaller than Table 310.16 would require for 200 A, because Table 310.12 permits dwelling service conductors to be rated at 83% of the service rating. Aluminum 4/0 is the overwhelmingly common choice on residential 200 A services, for cost reasons.
What is the 83% rule?
It is the allowance behind NEC Table 310.12. A dwelling's service or main power feeder may use conductors sized for 83% of the service rating rather than 100% — so a 200 A service needs conductors good for 166 A, not 200 A. The justification is diversity: a house's calculated load already includes demand factors, and the actual peak rarely approaches the service rating for long enough to matter thermally. Before the 2020 NEC this appeared as the 310.15(B)(7) allowance; it now has its own table.
Can 4/0 aluminum really carry 200 amps?
For a dwelling service, yes — that is exactly what Table 310.12 permits. On its own, Table 310.16 rates 4/0 aluminum at 180 A at 75 °C, which is why the same conductor is not acceptable as a general-purpose 200 A feeder. The 83% allowance is specific to dwelling services and main power feeders, and applying it anywhere else is a genuine code violation.
Does the 83% rule apply to a subpanel feeder?
Only if that feeder carries the entire load of the dwelling. A feeder to a detached garage, a shop subpanel, or any panel serving part of the load falls back to Table 310.16. This is where most online advice goes wrong: 4/0 aluminum is fine for a 200 A house service but is only good for 180 A as a garage feeder, so a 200 A garage subpanel needs 250 kcmil aluminum or 2/0 copper.
Can the neutral be smaller than the hot conductors?
Usually yes. NEC 220.61 permits the neutral to be sized for the maximum unbalanced load, which on a typical dwelling with 240 V appliances is less than the full ungrounded load. The floor is set by 250.24(C): the service neutral may never be smaller than the required grounding electrode conductor, because it carries fault current back to the source. In practice a 200 A service often uses a 2/0 aluminum neutral with 4/0 aluminum hots — which is what 4/0-4/0-2/0 SER and mobile-home feeder cable assemblies are built for.
Do I need to upsize for a long service run?
If drop pushes past 3%, yes — and long rural services from a pole often do. Set the run length above and the calculator upsizes automatically when the voltage-drop check fails, telling you it did so. Remember that upsizing the ungrounded conductors also triggers NEC 250.122(B) for the equipment grounding conductor on feeders; the Ground Wire Size Calculator handles that.
Copper or aluminum for a service?
Aluminum, almost always, on residential services — it costs substantially less for the same ampacity even after going up a size or two, and utility service drops are aluminum anyway. The requirements are that terminations be listed for aluminum (AL/CU or AL9CU marking) and that connections be made with the correct anti-oxidant compound and torque specification. Copper is preferred where space is very tight, in corrosive environments, or where a specification demands it.
Service conductors sized? Quote the upgrade in seconds.
A service upgrade is meter, panel, conductors, grounding, permit, and a day of labor. TradesQuote turns all of it into a detailed line-item estimate — quantities, unit prices, and totals — validated by a built-in quality control agent and ready for your client to sign.
AI line-item estimates
Quantities, unit prices, and totals generated instantly.
Knowledge base
Upload past jobs so estimates reflect your real pricing.
Shareable & signable
Clients review, accept, and sign from a public link.
No credit card required · 14-day free trial · Cancel anytime