Electrical Tools · NEC 2023 · Free

Ground Wire Size Calculator — EGC and GEC

"What size ground wire?" has two answers, because there are two different grounding conductors doing two different jobs. The equipment grounding conductor is sized from the breaker (Table 250.122). The grounding electrode conductor is sized from the service conductors (Table 250.66) — and then capped by the electrode you are connecting to. This calculator does both, and shows you exactly where the exception overrides the table.

Size the grounding conductor

EGC = fault-return path to the breaker. GEC = connection to the earth electrode.

Minimum grounding conductor

6 AWG copper

A 200 A overcurrent device requires a 6 AWG copper equipment grounding conductor.

Table used

Table 250.122

Exception applied

See the breakdown
Conductor type
Sized from
Table says
Electrode cap
250.122(B) upsize
Final size

Aluminum GECs may not contact earth or masonry and must be kept 18 inches above earth outdoors (250.64(A)). Parallel conductor sets and separately derived systems have additional rules.

The formula, explained in plain English

Two lookups and one multiplication. The hard part is knowing which conductor you are sizing.

# Equipment grounding conductor (Table 250.122)
EGC = lookup by overcurrent device rating
15 A → 14 · 20 A → 12 · 60 A → 10 · 100 A → 8 · 200 A → 6 · 400 A → 3  (copper)
# Grounding electrode conductor (Table 250.66)
GEC = lookup by largest service-entrance conductor
2 AWG or smaller → 8 · 1–1/0 → 6 · 2/0–3/0 → 4 · to 350 kcmil → 2  (copper)
# Then cap the GEC by the electrode (250.66(A)(B)(C))
rod, pipe, or plate → never larger than 6 AWG copper
concrete-encased → never larger than 4 AWG copper
ground ring → never larger than the ring conductor itself
# If the ungrounded conductors were upsized (250.122(B))
EGC cmil = table EGC cmil × (new conductor cmil ÷ original conductor cmil)

EGC follows the breaker

Its job is to carry fault current long enough to open that specific device, so the device rating is the only input. Conductor size doesn't enter it — unless 250.122(B) applies.

GEC follows the service

It has to handle whatever the service can deliver into the earth connection, so it scales with the service-entrance conductors rather than with any breaker.

The electrode is the bottleneck

A driven rod's resistance to earth is measured in ohms. Nothing above 6 AWG improves that connection, which is why 250.66(A) stops there. Concrete-encased rebar is better, so it earns 4 AWG.

Grounded ≠ grounding

The neutral is a grounded conductor carrying load current. The EGC is a grounding conductor carrying fault current only. They bond at exactly one point — the service disconnect — and nowhere else.

Worked examples

A branch circuit, the 200 A service where the table and the exception disagree, and the voltage-drop upsize that drags the ground up with it.

1

20 A kitchen circuit — EGC

20 A breaker · copper EGC · conductors not upsized.

Table 250.122, 20 A row → 12 AWG copper
(aluminum column would be 10 AWG)

Result: the 12 AWG bare or green conductor in standard 12/2 NM-B cable. Which is why the cable is built the way it is.

2

200 A residential service — both conductors

200 A main breaker · 3/0 copper service conductors · copper grounding conductors.

EGC: Table 250.122, 200 A → 6 AWG copper
GEC: Table 250.66, 3/0 copper → 4 AWG copper
  · to concrete-encased rebar → 4 AWG (250.66(B) cap is also 4)
  · to a driven rod only → 6 AWG (250.66(A) caps it)

Result: this is the source of the endless "is it 4 or 6?" argument. The table says 4 AWG; the electrode exception can pull it back to 6 AWG. Both are correct — for different electrodes.

3

Long 20 A run upsized for voltage drop — EGC

20 A breaker · conductors upsized from 12 AWG to 8 AWG for a long run · copper EGC.

base EGC from Table 250.122 = 12 AWG (6,530 cmil)
upsize ratio = 16,510 ÷ 6,530 = 2.53
required = 6,530 × 2.53 = 16,510 cmil
8 AWG copper (16,510 cmil — the smallest listed size that meets it)

Result: the EGC goes from 12 AWG to 8 AWG purely because the hots were upsized for voltage drop. NEC 250.122(B) is routinely missed on long runs, and it is exactly the kind of thing an inspector checks.

The two grounding tables

Table 250.122 sizes the equipment grounding conductor from the overcurrent device. Table 250.66 sizes the grounding electrode conductor from the service conductors — then the 250.66 exceptions cap it.

EGC — Table 250.122

By overcurrent device rating

Device Copper Aluminum
15 A 14 AWG 12 AWG
20 A 12 AWG 10 AWG
60 A 10 AWG 8 AWG
100 A 8 AWG 6 AWG
200 A 6 AWG 4 AWG
300 A 4 AWG 2 AWG
400 A 3 AWG 1 AWG
500 A 2 AWG 1/0 AWG
600 A 1 AWG 2/0 AWG
800 A 1/0 AWG 3/0 AWG
1000 A 2/0 AWG 4/0 AWG
1200 A 3/0 AWG 250 kcmil

GEC — Table 250.66

By largest service-entrance conductor

Service conductor (Cu) Copper Aluminum
2 AWG or smaller 8 AWG 6 AWG
1 or 1/0 AWG 6 AWG 4 AWG
2/0 or 3/0 AWG 4 AWG 2 AWG
over 3/0 through 350 kcmil 2 AWG 1/0 AWG
over 350 through 600 kcmil 1/0 AWG 3/0 AWG
over 600 through 1100 kcmil 2/0 AWG 4/0 AWG
over 1100 kcmil 3/0 AWG 250 kcmil

Caps: rod, pipe, or plate 6 AWG Cu (250.66(A)) · concrete-encased 4 AWG Cu (250.66(B)) · ground ring no larger than the ring (250.66(C)).

Sources & standards: NEC (NFPA 70) 2023 — Table 250.122 equipment grounding conductor sizing, 250.122(B) proportional increase, Table 250.66 grounding electrode conductor sizing, 250.66(A)(B)(C) electrode caps, 250.64(A) aluminum GEC restrictions, 250.24(A)(5) and 250.142 on neutral-to-ground bonding, 250.52 electrode types. Local amendments override the model code.

Frequently asked questions

Common questions about EGC and GEC sizing, and the electrode exceptions.

What size ground wire for a 200 amp service?

Two different answers, because a 200 A service involves two different grounding conductors. The equipment grounding conductor for a 200 A overcurrent device is 6 AWG copper from Table 250.122. The grounding electrode conductor depends on the service conductors — for typical 2/0 or 3/0 copper it is 4 AWG copper from Table 250.66, but if the only electrode is a driven ground rod, 250.66(A) caps it at 6 AWG. People arguing about "4 or 6" are usually both right about different conductors.

What's the difference between an EGC and a GEC?

An equipment grounding conductor is the fault-return path: it bonds metal enclosures back to the source so a ground fault has a low-impedance route that trips the breaker. It is sized from the overcurrent device rating (Table 250.122), because its job is to carry fault current long enough to open that device. A grounding electrode conductor connects the system to earth — lightning, static, and voltage stabilisation. It is sized from the service-entrance conductors (Table 250.66). Different jobs, different tables, and neither substitutes for the other.

Does the ground wire have to match the hot wires?

No, and it is normally much smaller. An equipment grounding conductor only carries current during a fault, for the fraction of a second before the breaker opens — so it is sized for that brief duty, not for continuous load. A 200 A feeder on 3/0 copper takes only a 6 AWG EGC. The exception is when the ungrounded conductors are upsized, which triggers 250.122(B).

Why does a ground rod only need 6 AWG?

Because NEC 250.66(A) says the portion of a grounding electrode conductor that is the sole connection to a rod, pipe, or plate electrode need not be larger than 6 AWG copper. The logic is that the rod itself is the limiting factor — a driven rod's contact resistance with the earth is measured in ohms, so a conductor larger than 6 AWG cannot improve the connection. Similar caps exist at 4 AWG for concrete-encased electrodes (250.66(B)) and at the ring size for a ground ring (250.66(C)).

Can I use aluminum for a grounding conductor?

Yes, with restrictions. Both tables list aluminum sizes. But NEC 250.64(A) prohibits aluminum or copper-clad aluminum grounding electrode conductors in direct contact with masonry or earth, or where subject to corrosive conditions, and requires them to be kept at least 18 inches above earth when used outdoors. In practice most GECs are copper for exactly this reason.

Do I upsize the ground when I upsize for voltage drop?

Yes. NEC 250.122(B) requires the EGC to be increased proportionally whenever the ungrounded conductors are increased in size — and it does not matter why you increased them. The ratio is by circular mils. If 12 AWG (6,530 cmil) goes to 8 AWG (16,510 cmil) for voltage drop, that is a factor of 2.53, so a 12 AWG EGC scales to 16,510 cmil and becomes 8 AWG. Toggle the upsize option above to run this. See the Voltage Drop Calculator for when upsizing is needed.

Is the neutral a grounding conductor?

No. The neutral is a grounded conductor — it carries normal unbalanced load current as part of the circuit. A grounding conductor carries current only during a fault. They are bonded together at exactly one point, the service disconnect, and must be kept separate everywhere downstream (NEC 250.24(A)(5) and 250.142). Bonding neutral to ground in a subpanel is one of the most common and most serious wiring errors, because it puts load current onto the grounding system.

Grounding sized? Price the service work in seconds.

Grounding is a handful of line items that inspectors always check. TradesQuote turns the whole job — conductors, clamps, rods, bonding, and labor — into a detailed line-item estimate with quantities and totals, validated by a built-in quality control agent.

AI line-item estimates

Quantities, unit prices, and totals generated instantly.

Knowledge base

Upload past jobs so estimates reflect your real pricing.

Shareable & signable

Clients review, accept, and sign from a public link.

No credit card required · 14-day free trial · Cancel anytime

More electrical calculators