Electrical Reference · Free

NEC Tables Reference

The lookup tables you actually reach for, on one page and free of pop-ups. Ampacity, derating factors, standard breaker ratings, conduit and box fill, and the two grounding tables — every one read from the same source our calculators use, so what you see here is what they compute.

Table 310.16

Conductor Ampacity

Allowable ampacities of insulated conductors rated up to 2,000 V, not more than three current-carrying conductors in a raceway, cable, or earth, at an ambient of 30 °C (86 °F). Under 110.14(C) the circuit is limited by the lowest-rated termination — usually 75 °C — so the 90 °C column is a derating starting point rather than a usable answer.

Size Copper Aluminum Circular mils
60 °C 75 °C 90 °C 60 °C 75 °C 90 °C
14 AWG 15 20 25 4,110
12 AWG 20 25 30 15 20 25 6,530
10 AWG 30 35 40 25 30 35 10,380
8 AWG 40 50 55 35 40 45 16,510
6 AWG 55 65 75 40 50 55 26,240
4 AWG 70 85 95 55 65 75 41,740
3 AWG 85 100 115 65 75 85 52,620
2 AWG 95 115 130 75 90 100 66,360
1 AWG 110 130 145 85 100 115 83,690
1/0 AWG 125 150 170 100 120 135 105,600
2/0 AWG 145 175 195 115 135 150 133,100
3/0 AWG 165 200 225 130 155 175 167,800
4/0 AWG 195 230 260 150 180 205 211,600
250 kcmil 215 255 290 170 205 230 250,000
300 kcmil 240 285 320 195 230 260 300,000
350 kcmil 260 310 350 210 250 280 350,000
400 kcmil 280 335 380 225 270 305 400,000
500 kcmil 320 380 430 260 310 350 500,000
600 kcmil 350 420 475 285 340 385 600,000

240.4(D) caps small conductors below these figures: 15 A for 14 AWG copper, 20 A for 12 AWG, 30 A for 10 AWG — and 15 A for 12 AWG aluminum, 25 A for 10 AWG. That is why 12 AWG copper reads 25 A here and still sits on a 20-amp breaker.

Table 310.12

Dwelling Services & Feeders

For a dwelling service, or a feeder carrying the entire load of a one-family dwelling, conductors may be sized at 83% of the rating. This does not reach an ordinary subpanel feeder — that sizes from Table 310.16 above.

Service or feeder rating Copper Aluminum / copper-clad 83% of rating
100 A 4 AWG 2 AWG 83.0 A
110 A 3 AWG 1 AWG 91.3 A
125 A 2 AWG 1/0 AWG 103.8 A
150 A 1 AWG 2/0 AWG 124.5 A
175 A 1/0 AWG 3/0 AWG 145.3 A
200 A 2/0 AWG 4/0 AWG 166.0 A
225 A 3/0 AWG 250 kcmil 186.8 A
250 A 4/0 AWG 300 kcmil 207.5 A
300 A 250 kcmil 350 kcmil 249.0 A
350 A 350 kcmil 500 kcmil 290.5 A
400 A 400 kcmil 600 kcmil 332.0 A
310.15(B)(1) & 310.15(C)(1)

Derating Factors

Both factors are applied to the ampacity from the conductor's insulation temperature column — normally 90 °C — and the result is then checked against the 75 °C termination limit. Starting from the 90 °C column is often what saves a conductor size.

Ambient temperature correction

310.15(B)(1) — base ambient 30 °C

Ambient 60 °C 75 °C 90 °C
≤ 10 °C (50 °F) 1.29 1.20 1.15
11–15 °C (52–59 °F) 1.22 1.15 1.12
16–20 °C (61–68 °F) 1.15 1.11 1.08
21–25 °C (70–77 °F) 1.08 1.05 1.04
26–30 °C (79–86 °F) 1.00 1.00 1.00
31–35 °C (88–95 °F) 0.91 0.94 0.96
36–40 °C (97–104 °F) 0.82 0.88 0.91
41–45 °C (106–113 °F) 0.71 0.82 0.87
46–50 °C (115–122 °F) 0.58 0.75 0.82
51–55 °C (124–131 °F) 0.41 0.67 0.76
56–60 °C (133–140 °F) 0.58 0.71
61–70 °C (142–158 °F) 0.33 0.58
71–80 °C (160–176 °F) 0.41

Conductor bundling adjustment

310.15(C)(1) — current-carrying conductors only

Conductors in the raceway Factor
1–3 conductors 1.00
4–6 conductors 0.80
7–9 conductors 0.70
10–20 conductors 0.50
21–30 conductors 0.45
31–40 conductors 0.40
41 or more conductors 0.35

Equipment grounding conductors never count. A neutral counts where it carries current. A nipple no longer than 24 in is exempt under Chapter 9, Table 1, Note 4.

240.6(A)

Standard OCPD Ratings

The only ratings fuses and inverse-time breakers come in. A calculation landing between two of them rounds up — there is no 33-amp breaker.

15 A 20 A 25 A 30 A 35 A 40 A 45 A 50 A 60 A 70 A 80 A 90 A 100 A 110 A 125 A 150 A 175 A 200 A 225 A 250 A 300 A 350 A 400 A 450 A 500 A 600 A

240.6(A) also lists additional standard fuse ratings of 1, 3, 6, 10 and 601 A and above, rarely seen on branch circuits.

Chapter 9, Tables 1, 4 & 5

Conduit Fill

Three tables working together: Table 1 gives the allowable percentage by conductor count, Table 4 the raceway's internal area, and Table 5 each conductor's area including insulation.

Table 1 — maximum percent fill

1 conductor

53%

2 conductors

31%

3 or more

40%

Two conductors is stricter than three — that is the code, not a typo, and it means the maximum count cannot be found by a single division. A nipple of 24 in or less goes to 60% under Note 4, and the 310.15(C)(1) adjustment factors do not apply to it.

Table 4 — raceway internal area, in²

Total (100%) area by type and trade size

Trade size EMTPVC Sch 40PVC Sch 80RMCIMC
1/2" 0.3040.2850.2170.3140.342
3/4" 0.5330.5080.4090.5490.586
1" 0.8640.8320.6880.8870.959
1-1/4" 1.4961.4531.2371.5261.647
1-1/2" 2.0361.9861.7112.0712.225
2" 3.3563.2912.8743.4083.630
2-1/2" 5.8584.6954.1194.8665.135
3" 8.8467.2686.4427.4997.922
4" 14.75312.55411.25812.88213.457

Table 5 — conductor area, in²

Including insulation

Size THHN / THWN-2 XHHW-2
1 AWG 0.1562 0.1534
2 AWG 0.1158 0.1146
3 AWG 0.0973 0.0962
4 AWG 0.0824 0.0814
6 AWG 0.0507 0.0590
8 AWG 0.0366 0.0437
10 AWG 0.0211 0.0243
12 AWG 0.0133 0.0181
14 AWG 0.0097 0.0139
1/0 AWG 0.1855 0.1825
2/0 AWG 0.2223 0.2190
3/0 AWG 0.2679 0.2642
4/0 AWG 0.3237 0.3197
250 kcmil 0.3970 0.3904
350 kcmil 0.5242 0.5153
500 kcmil 0.7073 0.6984

Note 7 permits rounding up where a calculation for conductors all of the same size produces a decimal of 0.8 or larger. Annex C bakes that in, which is why a pre-computed Annex C count can read one higher than a strict area calculation. Our conduit fill calculator computes strictly, so it is conservative by one at those boundaries.

314.16

Box Fill

Each conductor entering and terminating counts once. All internal cable clamps together count as one, at the largest conductor present. Each device yoke counts as two. All equipment grounding conductors together count as one. A conductor that both begins and ends inside the box — a pigtail — counts zero.

314.16(B) — volume per conductor

Conductor size Free space required
6 AWG 5.00 in³
8 AWG 3.00 in³
10 AWG 2.50 in³
12 AWG 2.25 in³
14 AWG 2.00 in³
16 AWG 1.75 in³
18 AWG 1.50 in³

Common box volumes

Table 314.16(A) plus trade sizes

Box Volume
3" × 2" × 2" device box 10.0 in³
3" × 2" × 2-1/4" device box 10.5 in³
3" × 2" × 2-1/2" device box 12.5 in³
3" × 2" × 2-3/4" device box 14.0 in³
3" × 2" × 3-1/2" device box 18.0 in³
Single-gang plastic box, 20.3 in³ 20.3 in³
Single-gang plastic box, 22.5 in³ 22.5 in³
4" square × 1-1/2" box 21.0 in³
4" square × 2-1/8" box 30.3 in³
4-11/16" square × 1-1/2" box 29.5 in³
4-11/16" square × 2-1/8" box 42.0 in³
250.66 & 250.122

Grounding Conductors

Two different conductors from two different tables. The equipment grounding conductor is keyed to the overcurrent device; the grounding electrode conductor is keyed to the largest ungrounded service-entrance conductor, then capped by which electrode it lands on.

Table 250.122 — equipment grounding conductor

By OCPD rating. Note there is no 30 A row.

OCPD up to Copper Aluminum
15 A 14 AWG 12 AWG
20 A 12 AWG 10 AWG
60 A 10 AWG 8 AWG
100 A 8 AWG 6 AWG
200 A 6 AWG 4 AWG
300 A 4 AWG 2 AWG
400 A 3 AWG 1 AWG
500 A 2 AWG 1/0 AWG
600 A 1 AWG 2/0 AWG
800 A 1/0 AWG 3/0 AWG
1000 A 2/0 AWG 4/0 AWG
1200 A 3/0 AWG 250 kcmil

Table 250.66 — grounding electrode conductor

By largest service-entrance conductor

Copper service Aluminum service Cu GEC Al GEC
2 AWG or smaller 1/0 AWG or smaller 8 AWG 6 AWG
1 or 1/0 AWG 2/0 or 3/0 AWG 6 AWG 4 AWG
2/0 or 3/0 AWG 4/0 AWG or 250 kcmil 4 AWG 2 AWG
over 3/0 through 350 kcmil over 250 through 500 kcmil 2 AWG 1/0 AWG
over 350 through 600 kcmil over 500 through 900 kcmil 1/0 AWG 3/0 AWG
over 600 through 1100 kcmil over 900 through 1750 kcmil 2/0 AWG 4/0 AWG
over 1100 kcmil over 1750 kcmil 3/0 AWG 250 kcmil

Then the caps: to a rod, pipe or plate the GEC need not exceed 6 AWG copper (250.66(A)); to a concrete-encased electrode, 4 AWG (250.66(B)); to a ground ring, no larger than the ring itself (250.66(C)). A metal water pipe has no cap.

Sources & standards: all tables are reproduced from NEC (NFPA 70) 2023 — Table 310.16, Table 310.12, 310.15(B)(1), 310.15(C)(1), 240.4(D), 240.6(A), Chapter 9 Tables 1, 4, 5 and 8 with Notes 4 and 7, Annex C, 314.16 and Table 314.16(A), Table 250.66 with 250.66(A)–(C), and Table 250.122. Baseline is NEC 2023; most states are on the 2020 or 2023 cycle, and NEC 2026 was published in 2025. These are planning aids — local amendments override the model code, and a licensed electrician plus the AHJ have final say on anything installed.

Let the calculator do the lookup

Every table on this page is read by one of our free calculators — same numbers, none of the cross-referencing.

Browse all electrical calculators →