A flex duct calculator sizes flexible (insulated) duct the same way as rigid metal — CFM plus friction rate — but with a critical difference: flex carries less air at the same nominal diameter. A flexible duct calculator must derate capacity or upsize one increment. A round duct calculator for rigid metal does not apply directly to flex without adjustment.

Flex vs Rigid Capacity

Nominal sizeRigid metal CFM (~0.10 fr)Flex duct CFM (derated)
6 in10080
8 in225180
10 in450360
12 in700560
14 in1,100880

Flex duct vs rigid metal CFM capacity

At every diameter flex duct carries 15–20% less air than rigid metal. The paired bars show why you must upsize one increment when substituting flex for rigid.

Flex duct carries 15–20% less than rigid at the same diameter due to ribbed wall friction. Poorly stretched flex (sagged, compressed, sharp bends) can lose 50%+ of rated capacity.

Flex Duct Sizing Rules

  1. Stretch fully extended — compressed flex reduces effective diameter
  2. Limit length — ACCA Manual D recommends max 15 ft per flex run where possible
  3. Upsize one increment — if rigid chart says 8 in, use 10 in flex
  4. Avoid sharp bends — use long-sweep elbows; kinks choke airflow
  5. Support every 4 ft — sagging reduces diameter and increases friction

Five flex duct installation rules

Each rule independently protects airflow capacity. Ignoring even one — especially sagging or sharp bends — can cut delivered CFM by 50% or more.

Round Duct Calculator Reference

Rigid round duct calculator output at 0.10 in.wg/100 ft:

CFMRound size
1006 in
2258 in
45010 in
70012 in

For flex, select the next size up from this round duct calculator table, or use our duct size calculator with flex derating.

Round duct to flex upsize reference

One size larger is the minimum adjustment when switching from rigid to flex. The blue bar is the rigid size; the teal bar is the correct flex size for the same airflow.

When Flex Is Appropriate

  • Last few feet to register — connects rigid trunk to ceiling or floor boot
  • Attic drops — where rigid routing is impractical
  • Retrofit — adding a supply to an existing room

Avoid flex for long trunk runs, horizontal spans over 15 ft, or any run you cannot inspect and support properly.

See HVAC Duct Calculator Guide and Online Ductulator Guide for rigid duct sizing.

Use the Free Calculator

HVAC Duct Size Calculatorflex duct calculator and round duct calculator with friction rate control.


FAQ

How do I use a flex duct calculator?

Size for CFM at target friction rate, then upsize one diameter from the rigid-metal chart — or derate flex capacity by 15–20%.

What is the difference between flex duct calculator and round duct calculator?

Round duct calculator assumes smooth rigid metal. Flex duct calculator must account for higher friction from corrugated walls.

Can flexible duct replace rigid trunk lines?

Not recommended. Flex is for short branch connections. Long flex trunks sag, restrict airflow, and fail inspection in many jurisdictions.

What round duct size for 400 CFM in flex?

Rigid chart says 10 in for ~450 CFM. Use 12 in flex for 400 CFM to maintain acceptable velocity and friction.